FOR IMPORTERS, DISTRIBUTORS & RETAIL PROGRAMSSales Department · (+84) 868 848 620
RW90
Building wire

RW90

Canadian thermoset insulated power conductor for recognized raceways.

Canada
Sizes, construction & electrical data
RW90 / TECHNICAL DATA

Sizes, construction & electrical data

Conductor material
Copper (Cu)
Insulation material
XLPE
Rated voltage
600 V
Maximum conductor temperature
90°C
Copper / XLPE · 600 V · circuit sizes
ConfigurationNominal area / conductormm²Conductor sizeAWG / kcmilStrands per conductorInsulation wallmmOverall dimensions / diametermmApproximate cable weightkg/kmMinimum bend radiusmmMaximum pulling tensionNDC conductor resistance at 25°CΩ/kmAC resistance at 75°CΩ/kmInductive reactance at 60 HzΩ/kmReference ampacity, 90°C columnASelection
14 AWG2.08114Solid0.7623.25123.812.7142.38.63210.40.1925
14 AWG2.0811470.7623.42925.312.7142.38.63210.40.1925
12 AWG3.30912Solid0.7623.65835.715.24231.35.4536.5680.17730
12 AWG3.3091270.7623.88637.215.24231.35.4536.5680.17730
12 AWG3.3091270.7623.88637.215.24142.35.4536.5680.17730
10 AWG5.26110Solid0.7624.19155.117.78369.23.4124.1110.16440
10 AWG5.2611070.7624.44556.617.78231.33.4124.1110.16440
10 AWG5.2611070.7624.4965817.78369.23.4124.1110.16440

Typical applications

Services, feeders and branch circuits in wet/dry locations.

Design advantages

XLPE insulation supports moisture and heat resistance.

Selection notes

Do not infer direct burial from RW90 alone; verify RWU90 or additional rating.

Standards to review

CSA C22.2 No. 38; CSA C22.1

Related cable families

TGS · VIETNAM

Let’s connect your next project.

Send your cable type, destination market and volume. We will review the next steps with you.