FOR IMPORTERS, DISTRIBUTORS & RETAIL PROGRAMSSales Department · (+84) 868 848 620
XHHW-2
Building wire

XHHW-2

Thermoset XLPE insulated conductor for building power distribution.

United StatesLatin America
Sizes, construction & electrical data
XHHW-2 / TECHNICAL DATA

Sizes, construction & electrical data

Dimensional and electrical reference · Copper · 600 V

Conductor material
Copper (Cu)
Insulation material
XLPE
Rated voltage
600 V
Maximum conductor temperature
90°C
Ampacity basis
2023 NEC Table 310.16; applicable correction and termination rules apply
Dimensional and electrical reference · Copper · 600 V
ConfigurationNominal area / conductormm²Conductor sizeAWG / kcmilStrands per conductorDiameter over bare conductormmInsulation wallmmDiameter over insulationmmOverall dimensions / diametermmCopper weightkg/kmApproximate cable weightkg/kmMinimum bend radiusmmMaximum pulling tensionNDC conductor resistance at 25°CΩ/kmAC resistance at 75°CΩ/kmInductive reactance at 60 HzΩ/kmReference ampacity, 75°C columnAReference ampacity, 90°C columnASelection
8 AWG8.366873.6071.1435.8936.04574.495.225.4587.22.1422.6570.1715055
6 AWG13.302674.4961.143—6.96120.5144.427.94929.71.3481.6240.1676575
4 AWG21.151475.7151.1438.0018.153190.5220.233.021481.30.8461.050.1578595
3 AWG26.67376.4011.1438.6878.839241.1273.835.561868.30.6730.8330.154100115
2 AWG33.631277.1881.1439.4749.627303.6339.338.12357.60.5310.6590.148115130
1 AWG42.4081198.1791.39710.97311.1383.9431.643.182975.90.420.5220.151130145
1/0 AWG53.4751/0199.1951.39711.98912.09485.1538.748.263754.30.3350.4170.144150170
2/0 AWG67.4312/01910.2871.39713.08113.208610.1669.753.344732.90.2690.3350.141175195
3/0 AWG85.0293/01911.5821.39714.37614.478770.9836.358.425969.50.210.2590.138200225
4/0 AWG107.2194/01913.0051.39715.79915.9974.71047.763.57526.40.1670.2070.135230260
250 kcmil126.6772503714.1731.65117.47517.2721147.41239.668.588896.40.1410.1740.135255290
300 kcmil152.0123003715.5191.65118.82118.59313781477.773.6610675.70.1180.1480.135285320
350 kcmil177.3483503716.7891.65120.09119.7871607.21714.478.74124550.1020.1280.131310350
400 kcmil202.6834003717.9321.65121.23420.9041837.9195183.8214234.30.0890.1150.131335380
500 kcmil253.3545003720.0411.65123.34322.9622296.22422.791.4417792.90.0690.0890.128380430
600 kcmil304.0246006121.9962.03226.0625.6032756.12922.812721351.50.0590.0790.128420475
700 kcmil354.6957006123.7492.03227.81327.3053215.93394.5137.16249100.0490.0660.125460520
750 kcmil380.0317506124.5872.03228.65128.1183445.13629.6139.726689.30.0460.0620.125475535
1000 kcmil506.70710006128.3722.03232.43632.63945944811.2162.5635585.80.0360.0520.121545615

Typical applications

Services, feeders and branch circuits in recognized raceways.

Design advantages

Heat and moisture resistant XLPE insulation.

Selection notes

Tray, sunlight and burial ratings depend on size and product marking.

Standards to review

UL 44; NFPA 70