FOR IMPORTERS, DISTRIBUTORS & RETAIL PROGRAMSSales Department · (+84) 868 848 620
NMD90
Building wire

NMD90

Canadian nonmetallic sheathed cable for permitted building wiring.

Canada
Sizes, construction & electrical data
NMD90 / TECHNICAL DATA

Sizes, construction & electrical data

Dimensional and electrical reference · Copper · 300 V

Conductor material
Copper (Cu)
Insulation material
PVC + nylon
Rated voltage
300 V
Maximum conductor temperature
90°C
Jacket / armour
PVC
Dimensional and electrical reference · Copper · 300 V
ConfigurationNominal area / conductormm²Conductor sizeAWG / kcmilInsulated conductorsStrands per conductorBare bonding conductorNo. × AWGDiameter over bare conductormmInsulation wallmmOuter jacket wallmmOverall dimensions / diametermmCopper weightkg/kmApproximate cable weightkg/kmDC conductor resistance at 25°CΩ/kmAC resistance at 75°CΩ/kmInductive reactance at 60 HzΩ/kmMinimum bend radiusmmReference ampacity, 75°C columnAReference ampacity, 90°C columnASelection
14/22.081142Solid1x141.6260.8890.7624.978x10.05855.1102.78.63210.40.1940.642025
14/32.081143Solid1x141.6260.8890.7629.85574.4133.98.63210.40.1938.12025
12/23.309122Solid1x142.0320.8890.7625.41x10.92275.91315.4536.5680.17740.642530
12/33.309123Solid1x142.0320.8890.76210.871107.1175.65.4536.5680.17743.182530
10/25.261102Solid1x122.5650.8890.7625.944x12.395122184.53.4124.1110.16450.83540
10/35.261103Solid1x122.5650.8890.76212.167171.12503.4124.1110.16448.263540
8/28.3668271x103.5811.0161.1438.026x17.628197.9312.52.1422.5790.17171.125055
8/38.3668371x103.5811.0161.14316.129276.8421.22.1422.5790.17163.55055
6/213.3026271x84.4961.271.1439.5x20.32317504.51.3481.6240.16781.286575
6/313.3026371x84.4961.271.14319.685442644.41.3481.6240.16778.746575
4/221.1514271x85.7151.271.52421.311462.86890.8461.0170.15783.828595
3/226.673271x66.4011.272.03223.8610.1907.80.6730.8070.15493.98100115
3/326.673371x66.4011.272.03226.137854.21223.30.6730.8070.154129.54100115
2/333.631237—7.1631.272.03225.1711044.71282.80.5310.640.14899.06115130

Typical applications

Exposed dry or concealed dry/damp residential wiring.

Design advantages

Insulated conductors and bonding wire in one sheath.

Selection notes

Not for wet locations or direct burial. Installation temperature and terminations limit use.

Standards to review

CSA C22.2 No. 48; CSA C22.1

Related cable families

TGS · VIETNAM

Let’s connect your next project.

Send your cable type, destination market and volume. We will review the next steps with you.