FOR IMPORTERS, DISTRIBUTORS & RETAIL PROGRAMSSales Department · (+84) 868 848 620
USE-2
Service & underground

USE-2

Thermoset insulated underground service-entrance conductor.

United States
Sizes, construction & electrical data
USE-2 / TECHNICAL DATA

Sizes, construction & electrical data

Dimensional and electrical reference · Copper · 600 V

Conductor material
Copper (Cu)
Insulation material
XLPE
Rated voltage
600 V
Maximum conductor temperature
90°C
Ampacity basis
2023 NEC Table 310.16; applicable correction and termination rules apply
Dimensional and electrical reference · Copper · 600 V
ConfigurationNominal area / conductormm²Conductor sizeAWG / kcmilStrands per conductorDiameter over bare conductormmInsulation wallmmDiameter over insulationmmOverall dimensions / diametermmCopper weightkg/kmApproximate cable weightkg/kmMinimum bend radiusmmDC conductor resistance at 25°CΩ/kmAC resistance at 75°CΩ/kmInductive reactance at 60 HzΩ/kmReference ampacity, 75°C columnAReference ampacity, 90°C columnASelection
14 AWG2.0811471.8031.1434.0894.19117.931.317.788.63210.7120.192025
12 AWG3.30912Solid2.0571.1434.3434.44528.341.717.785.4536.7680.1772530
12 AWG3.3091272.2611.1434.5474.64829.843.217.785.4536.7680.1772530
10 AWG5.2611072.871.1435.1565.25847.66420.323.4124.2360.1643540
8 AWG8.366873.6071.5246.6556.807—102.727.942.1422.6570.1715055
6 AWG13.302674.5211.5247.5697.722120.5153.330.481.3481.6730.1676575
4 AWG21.151475.7151.5248.7638.915190.5230.735.560.8461.050.1578595
3 AWG26.67376.4011.5249.4499.601241.1284.238.10.6730.8330.154100115
2 AWG33.631277.1881.52410.23610.389303.6352.740.640.5310.6590.148115130
1 AWG42.4081198.1792.03212.24312.421383.9458.450.80.420.5220.151130145
1/0 AWG53.4751/0199.1952.03213.25913.411483.7565.553.340.3350.4170.144150170
2/0 AWG67.4312/01910.2872.03214.35114.529610.1699.458.420.2690.3350.141175195
3/0 AWG85.0293/01911.5822.03215.64615.799770.9869.163.50.210.2590.138200225
4/0 AWG107.2194/01913.0052.03217.06917.221974.71083.468.580.1670.2070.135230260
250 kcmil126.6772503714.1732.41318.99918.8471147.41287.376.20.1410.1740.135255290
300 kcmil152.0123003715.5192.41320.34520.16813781526.981.280.1180.1480.135285320
350 kcmil177.3483503716.7892.41321.61521.8691608.71772.486.360.1020.1280.131310350
400 kcmil202.6834003717.9322.41322.75822.4791837.92007.588.90.0890.1150.131335380
500 kcmil253.3545003720.0412.41324.86724.5362296.22485.299.060.0690.0890.128380430
600 kcmil304.0246006121.9962.79427.58427.2292757.62994.2137.160.0590.0790.128420475
750 kcmil380.0317506124.5872.79430.17529.7433445.13708.5149.860.0460.0620.125475535
1000 kcmil506.70710006128.3722.79433.9634.2654595.54903.5170.180.0360.0520.121545615

Typical applications

Underground service routing and permitted direct burial.

Design advantages

Moisture-resistant XLPE power insulation.

Selection notes

USE-2 alone does not establish indoor flame-rated use; verify additional RHH/RHW-2 marking.

Standards to review

UL 854; UL 44

Related cable families

TGS · VIETNAM

Let’s connect your next project.

Send your cable type, destination market and volume. We will review the next steps with you.

Request a quote