Copper / XLPE / aluminium armour · 600 V
- Insulation / armour
- XLPE (RW90) / aluminium
- Rated voltage / temperature
- 600 V / 90°C; cold bend −40°C
- Ampacity basis
- 2018 CEC Table 2; 30°C ambient; in conduit; Rule 14.104(2) applies
- Installation environment
- Dry locations
| ConfigurationAWG / cores | Nominal area / conductormm² | Insulated conductors | Insulation wallmm | Bond / ground conductorNo. × AWG | Overall dimensions / diametermm | Approximate cable weightkg/km | Reference ampacity, 60°C columnA | Reference ampacity, 75°C columnA | Reference ampacity, 90°C columnA | Selection |
|---|---|---|---|---|---|---|---|---|---|---|
| 14/2 | 2.081 | 2 | 0.76 | 1 × 14 | 11.48 | 134 | 15 | 20 | 25 | |
| 12/2 | 3.309 | 2 | 0.76 | 1 × 14 | 12.34 | 165 | 20 | 25 | 30 | |
| 10/2 | 5.261 | 2 | 0.76 | 1 × 12 | 13.41 | 220 | 30 | 35 | 40 | |
| 14/3 | 2.081 | 3 | 0.76 | 1 × 14 | 12.07 | 162 | 15 | 20 | 25 | |
| 12/3 | 3.309 | 3 | 0.76 | 1 × 14 | 12.90 | 204 | 20 | 25 | 30 | |
| 10/3 | 5.261 | 3 | 0.76 | 1 × 12 | 14.07 | 280 | 30 | 35 | 40 | |
| 14/4 | 2.081 | 4 | 0.76 | 1 × 14 | 13.46 | 193 | 15 | 20 | 25 | |
| 12/4 | 3.309 | 4 | 0.76 | 1 × 14 | 13.82 | 246 | 20 | 25 | 30 | |
| 10/4 | 5.261 | 4 | 0.76 | 1 × 12 | 15.75 | 363 | 30 | 35 | 40 | |
| 3/3 | 26.67 | 3 | 1.143 | 1 × 6 | 26.36 | 1198 | 85 | 100 | 115 |